| Availability: | |
|---|---|
| Quantity: | |
GCB-E261 125kW / 261kWh
E-ABLE POWER
Liquid-Cooled Energy Storage Cabinet
| E-ABLE POWER — PRODUCT DATASHEET COMMERCIAL ENERGY STORAGE SOLUTIONS | C&I ENERGY STORAGE125kW / 261kWhLIQUID COOLING |
GCB-E261 Series | Liquid-Cooled Energy Storage Cabinet GCB-E261 125kW / 261kWh Liquid-Cooled Energy Storage CabinetGCB-E261 is a 125kW / 261kWh liquid-cooled energy storage cabinet built with LFP 314Ah cells. The battery is rated at 832V with a 728-936V voltage range. The cabinet uses liquid cooling with a 50% ethylene glycol aqueous solution, aerosol fire protection and a 10-year warranty. | ![]() |
| Rated Power / Energy | 125kW / 261kWh | Battery Cell | LFP 314Ah |
| Battery Pack | 166.4V / 314Ah | Battery Voltage | 832V; 728-936V range |
| Cooling | Liquid cooling | Protection / Fire | IP54 / Aerosol |
| Standard Current | 157A charge / 157A discharge | Warranty | 10 Years |
Liquid-Cooled Thermal ControlThe specified cooling method is liquid cooling, using an ethylene glycol aqueous solution at 50%:50% for consistent cell temperature across the pack and stable output in high ambient conditions. | 261kWh LFP StorageLFP 314Ah cells, five battery packs in series, 261kWh rated energy and 0.5P rated charge-discharge rate — long cycle life and low total cost of ownership. | Outdoor Cabinet ProtectionIP54 protection, aerosol fire protection, heat and smoke detection, and operation from -20 to 50°C are specified for outdoor commercial deployment. |
| Category | Parameter | Specification |
|---|---|---|
| System | Type / power / energy | Liquid-cooled energy storage cabinet / 125kW / 261kWh |
| Battery | Cell / pack / configuration | LFP 314Ah / 166.4V 314Ah / 1P260S |
| Voltage / power / current | 832V (5 modules series); 728-936V; 130.5kW; 157A / 157A standard current | |
| Cycle life | 8,000 cycles at 90% DOD, EOL 70% | |
| Cabinet | Dimensions / weight / protection | 970 x 1420 x 2320mm / approximately 3t / IP54 |
| Environment | -20 to 50°C; RH <=95%; altitude <2,000m | |
| Cooling / coolant | Liquid cooling / ethylene glycol aqueous solution (50%:50%) | |
| Fire protection / detector | Aerosol / heat and smoke detection | |
| Warranty | Warranty period | 10 years |
Table 1.0 — GCB-E261 technical specifications. Final configuration, interfaces, operating limits and documentation are confirmed per project.
The datasheet specifies liquid cooling with a 50%:50% ethylene glycol aqueous solution — delivering more consistent cell temperatures than air cooling, especially at high charge/discharge rates.
The cabinet is rated at 261kWh, with 832V battery voltage (728-936V range) and five battery packs in series, built with LFP 314Ah cells.
The specified operating temperature is -20 to 50°C, relative humidity is RH <=95%, and altitude is below 2,000m.
Confirm site conditions, grid interface, installation layout and the final technical configuration before project release. E-Able Power engineering provides a complete technical proposal within 2–3 business days.
| | | |
Send your load profile, site conditions and requirements for a project-specific proposal. Battery configuration, grid interface and cooling loop design are confirmed per project.
content is empty!